Application
Installation wire for use in pipe or skirting systems for wiring in installation pipes and building installations, wiring of cable ducts, as well as switch boxes, control panels, appliances, etc.
Note
Also available in a PVC 90 C version H07V2-U Eca / H07V2-R Eca and a halogen-free version Z1Dzh Cca.
Certificates
NEN-EN
50525-2-31
VD Eca complies with the fire class Eca according to NEN-EN 50575.
For applications in buildings with a low fire risk according to NEN 8012.
Easy to pull into pipe, without damaging the insulation.
Good electrical properties.
Great mechanical strength.
UV and ozone resistant
Nom. voltage U0 (V): 450
Nom. voltage U (V): 750
Test voltage (kV): 2.5
Oil resistant: No
Max. permissible conductor temperature (°C): 70
Min. temperature, fixed installation: -40
Max. temperature, fixed installation: 50
Cold-resistant according to EN 60811: No
UV-resistant: Yes
Outdoor installation: Yes
Min. temperature at installation: 5
Max. temperature at installation: 50
Fire retardant: According to EN 13501-6
Halogen-free: No
Low smoke: No
CPR fire class: Eca
CPR smoke class: Not applicable
CPR class burning particles: Not applicable
CPR class acidity: Not applicable
Conductor material: Copper
Surface conductor: Blank
Core insulation material: Polyvinyl chloride (PVC)
Construction: 2.5 mm²
Conductor composition: Class 1 = solid
Core color: Green/yellow
Nominal cable diameter: 3.3
Weight (kg / km): 30
Weegbree 15-17
4941 VT
+31 (0)88 – 8808 188
verkoop@dtcelektro.nl
Galliërsweg 34
5349 AT
+31 (0)412 – 480 190
oss@dtcelektro.nl
Copyright DTC Elektro © 2022
Let wel: online staat slechts een kleine greep uit ons assortiment.
Kan je een product niet vinden? Neem dan direct contact met ons op.
Kan je een product niet vinden? Neem dan contact met ons op.